Honeywell V4055 Automobile Parts User Manual


 
V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
customer.honeywell.com
® U.S. Registered Trademark
© 2010 Honeywell International Inc.
60-2309—13 E.K. Rev. 02-10
Printed in U.S.A.
Each replacement assembly contains the bonnet assembly,
two rubber seals, and a tube of grease. It must be used only
on the type of valve indicated above.
Fig. 6. Typical application of a V4055D/V5055C/V5097D or V4055E/V5055E/V5097E combination to meet Factory Mutual
or Underwriters Laboratories Inc. approved requirements for Proof-of-Closure Switch (valve seal overtravel interlock).
Table 9. Gas Valve Replacement Seals.
Replacement Seal
Assy # Valve Size (in in.)
133393A 3/4, 1, 1-1/4, 1-1/2
133392A 2, 2-1/2, 3
137253A 4
3
1
1
3
4
9
10
B
R
W
B
R
W
11
WIRING SUBBASE TERMINAL STRIP (4)
R414OL FLAME SAFEGAURD CONTROLS
2
LOCKOUT
INTERLOCKS
(INCL. AIRFLOW
SWITCH)
BURNER
CONTROLLER
LIMITS
ALTERNATE
LOW-FIRE
SWITCH
ALARM
HIGH-FIRE
COMMON
MODULATE
LOW-FIRE
SERIES 90
CONTROLLER
SERIES 90
FIRING RATE
MOTOR
120V, 60 HZ
POWER
SUPPLY
L1 (HOT)
L2
RECTIFYING FLAME
ROD, RECTIFYING
PHOTOCELL, OR INFRARED
(LEAD SULFIDE)
FLAME DETECTOR
10 SECOND
INTERRUPTED
PILOT/IGNITION
15 SECOND
INTERRUPTED
PILOT/IGNITION
BURNER
MOTOR
LOW-FIRE
SWITCH
HIGH-FIRE
SWITCH
C7012A, C, E,F
OR C7076A
ULTRAVIOLET
FLAME DETECTOR
C7027A, C7035A, OR
C7044A, ULTRAVIOLET
FLAME DETECTOR
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
USE ALL NEC CLASS 1 WIRING.
3
PROOF-OF-CLOSURE SWITCH IN PREIGNITION INTERLOCK CIRCUIT;
SWITCH IS CLOSED NC-C WHEN ACTUATOR IS DE-ENERGIZED.
V4055D OR E
L1
1 2
18
17
16
15
14
C
NC
NO
L2
12
13
F
5
6
7
8
G
BLUE WHITE
YELLOW
BLUE
WHITE
WHITE
BLACK
BLACK
L2
L2
L1
OR
OR
MASTER
SWITCH
M7335