Honeywell V4055 Automobile Parts User Manual


 
V4055A,B,D,E ON-OFF FLUID POWER GAS VALVE ACTUATOR
3 60-2309—13
Table 3. V4055A,D Electrical Ratings.
a
50 Hz power supply.
b
60 Hz power supply.
c
230 Vac, 50 Hz power supply.
d
230 Vac, 60 Hz power supply.
Table 4. V4055B,E Electrical Ratings.
a
230 Vac, 50 Hz power supply.
b
230 Vac, 60 Hz power supply.
Auxiliary Switch and Proof-of-Closure Switch Ratings:
See Table 5.
Table 5. Auxiliary Switch and Proof-of-Closure
Switch Ratings (1/2 hp [0.37kW]
a
).
a
Maximum total connected power to both switches (if used) is
1800 VA.
Mounting Dimensions: See Fig. 1 and Table 7.
Damper Shaft: Shaft is 3/8 in. (9.5 mm) square, for use with
7616BR Damper Crank Arm (ordered separately) and with or
without damper shaft return spring.
Maximum Damper Shaft Rotation: 52 angular degrees.
Maximum Force: 2-11/16 in. (68.3 mm) radius for 7616BR
Damper Crank Arm ordered separately (see Accessories
section).
NOTE: Damper shaft drives damper crank arm in one
direction only; optional return spring is available on
damper shaft to turn damper crank arm in opposite
direction. See Table 6.
Table 6. Actuator Torque (With and
Without Return Spring).
Approvals:
Underwriters Laboratories Inc. Listed: File No. MH1639, Guide
No. YIOZ.
Factory Mutual: Listed.
Canadian Standards Association certified: General Listed file
numbers 158158 Class 3371
For U.S.A. and Canada: certified 60 Hz models only.
Swiss Re (Formerly GeGap/IRI) Acceptable.
Some V4055 Actuators are approved as Class A valves in
accordance with EN161:
When used with V5055 Valves: Pin: CE-0063AR1359.
When used with VE5000 Series Valves: Pin: CE-
0063AP3075.
Voltage and Frequency
Opening (Standard) Opening (Fast) Holding
Inrush (W) (A) VA) Inrush (W) (A) (VA) (W) (A) (VA)
100/50-60
a
43.0 0.91 91 58.0 1.30 130 10.4 0.16 16
100/50-60
b
33.0 0.6 67 43.0 0.91 91 8.4 0.14 14
120/60 3.9 50.0 0.94 115 5.4 71.0 1.33 160 9.5 0.12 14
200/50-60
a
68.0 0.79 158 88.0 1.10 220 10.6 0.09 18
200/50-60
b
48.0 0.52 104 63.0 0.72 144 9.0 0.07 14
220/50 1.6 55.5 0.55 121 3.0 76.0 0.80 176 9.0 0.06 14
240/50 81.5 0.79 190 95.0 1.00 240 9.1 0.06 14
240/60 2.6 51.0 0.45 115 4.0 71.5 0.68 160 9.2 0.06 14
220-240/50-60
c
70.3 0.59 136 7.2 0.07 16
220-240/50-60
d
58.6 0.46 106 5.9 0.06 14
Voltage and
Frequency
Opening (Standard) Opening (Fast) Holding
Inrush (W) (A) (VA) Inrush (W) (A) (VA) (W) (A) (VA)
120/60 60 0.94 115 60.0 0.94 115 9.5 0.16 19
220-240/50-60
a
68.9 0.58 133 6.7 0.08 18
220-240/50-60
b
58.2 0.46 106 5.3 0.06 14
Load 120V 240V
Full Load 9.8A 4.9A
Locked Rotor 58.8A 29.4A
V4055 Model
-40°F to +20°F
(-40°C to -7°C)
20°F to 150°F
(-7°C to +66°C)
lb N lb N
With return spring 5 22.2 10 44.5
Without return spring 5 22.2 20 89.0