Honeywell ML6195 Automobile Parts User Manual


 
PRODUCT DATA
® U.S. Registered Trademark
Copyright © 1997 Honeywell Inc. • All Rights Reserved
ML6195, ML6295 Spring Return
Direct Coupled Actuators
APPLICATION
The ML6195 Spring Return Direct Coupled Actuator (DCA) is a
floating control motor. Use with controls that provide switched or
floating single-pole, double-throw (spdt) (Series 60) control
output to operate dampers or valves in heating, ventilation, and
air conditioning (HVAC) applications. For hydronic valve
applications, a complete line of brackets and linkages are
available for mounting Honeywell DCAs on globe valves and on
Honeywell ball valves. The ML6295 includes an internal,
electrically isolated feedback potentiometer. This potentiometer
provides indication of the shaft coupling position and can be
used for rebalancing an external control circuit.
FEATURES
Brushless DC motor achieves sophisticated control of
speed, torque and braking.
Provides 142 lb-in. (16 N•m) torque.
Mounts directly on 3/8 in. to 1 in. (9 to 25 mm) round
and 1/4 in. to 3/4 in. (6 to 18 mm) square shafts.
Self-centering shaft coupling minimizes installation
time.
Spring return direction is field-selectable to simplify
installation.
Manual override permits unpowered positioning to
simplify installation and troubleshooting. Deactivation
of interlock is manual or automatic when power is
restored.
Highly-visible position indicator facilitates setup,
checkout and troubleshooting.
Rugged, lightweight all-metal alloy housing provides
durability.
Integral conduit connection.
Integral adjustable range-stop.
Models available with two fully adjustable line voltage
auxiliary switches.
Contents
Application........................................................................... 1
Features .............................................................................. 1
Specifications ...................................................................... 2
Ordering Information ........................................................... 2
Installation ........................................................................... 3
Operation ............................................................................ 6
Checkout ............................................................................. 7
63-2537-1
129-235