Generac Power Systems 0F9765MNL Automobile Parts User Manual


 
4
3.0L GAS ENGINE SERVICE RECOMMENDATIONS
Maintenance Tasks Level 1 Level 2 Level 3 Level 4
Recommended to
be done monthly/
10 hrs.
Task
Comp.
(Date-
Initials)
Required to be
done 3 months/
Break-in /30 hrs.
Task
Comp.
(Date-
Initials)
Required to
be done Semi-
Annually/50 hrs.
Task
Comp.
(Date-
Initials)
Required to be done
Annually/ 100 hrs.
Task
Comp.
(Date-
Initials)
1. Disable the unit from operating
per the first page warning.
2. Check the engine oil level. Adjust
as necessary.
3. Check the engine coolant level.
Adjust as necessary.
4. Check the engine coolant ther-
mal protection level. Correct as
necessary.
5. Check the natural gas delivery
system on gas engine driven
units. Tighten connections as
necessary.
6. Check the diesel fuel supply
level for diesel engine driven
units. Fill as necessary.
7. Drain water and sediment from
the diesel fuel tank on diesel
engine driven units.
8. Drain water from the fuel line
water separator on diesel
engine driven units if the unit is
equipped with one.
9. Check the air inlets and outlets
for debris. Clean as necessary.
10. Check the battery electrolyte
level if accessible. Adjust as
necessary.
11. Check the battery posts,
cables, and charger for loose
connections, corrosion, and
proper operation. Correct as
necessary.
12. Check the unit wiring for loose
connections, corrosion, and
damage. Correct as necessary.
13. Check the engine accessory
drive belts for wear, weather
cracking, and damage. Replace
as necessary.