6F3B0253
252 T1-16S User’s Manual
7. Instructions
< Write command mode (Mode 3) >
When the instruction input comes ON with the operand B+1 is 3, the Write command mode
(mode 3) is selected. In this mode, the T1-16S sends the user specified Write command to the
Inverter specified by the operand B, and repeats.
Sends the specified command with command data to #n Inverter
Checks the acknowledge
The target Inverter number #n is specified by the operand B.
The scan execution status and the Inverter communication status are stored in the operand
B+2 to B+7.
The command code and the command data setting registers are indirectly specified by the
operand A and A+1.
When the instruction input is reset to OFF, the operation is stopped after receiving the
response from the Inverter.
Example
Data table designation Parameter & status RS-485 port
D1000 4 RW200 5 D1010 H0030 (fixed)
D1001 3010 RW201 3 (mode 3) D1011 0 (fixed)
RW202 Execution status
RW203 Comm error code
RW204
RW205 Inverter comms
RW206 status map
RW207
When the data for each operand are set as above, the following operation condition is specified.
• RW200=5 ⇒ The target Inverter number is 5. Therefore T1-16S communicates with #5 Inverter.
• D1000=4 & D1001=3010 ⇒ D3010 is specified as the command code setting register and D3011 is
specified as the command data setting register.
Data table:
Register Data contents Signal direction
D3010 Command code
D3011 Command data
→ Write
Example operation:
For example, to write the acceleration time parameter (10 seconds) to the #5 Inverter, set the
command code H0009 into D3010 and the value 100 into D3011.
For the command code and the command data format, refer to your Inverter manual.
Repeat