![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/3/6d/36dd580f-a169-498b-8bdb-2c7ef252abe4/36dd580f-a169-498b-8bdb-2c7ef252abe4-bgbe.png)
6F3B0253
188 T1-16S User’s Manual
7. Instructions
FUN 106
D<
Double-word less than
Expression
Input −[ A+1⋅A D< B+1⋅B ]− Output
Function
When the input is ON, the double-word data of A+1⋅A and B+1⋅B are compared, and if A+1⋅A is
less than B+1⋅B, the output is turned ON.
Execution condition
Input Operation Output
OFF No execution OFF
ON Execution
A+1⋅A < B+1⋅B
ON
A+1⋅A ≥ B+1⋅B
OFF
Operand
Name Device Register Constant Index
X Y R S T. C. XWYWRWSW T C D I J K
A Compared
data
√√√√√√√ √
B Reference
data
√√√√√√√ √
Example
When R010 is ON, the data of D0101⋅D0100 is compared with the constant data 427780, and
if the data of D0101⋅D0100 is less than 427780, R014 is turned ON.
If the data of D0101⋅D0100 is 250000, R014 is turned ON.
D0101⋅D0100 250000 < Constant 427780 R014 is ON
If the data of D0101⋅D0100 is 430000, R014 is turned OFF.
D0101⋅D0100 430000 ≥ Constant 427780 R014 is OFF
Note
• This instruction deals with the data as double-word integer (-2147483648 to 2147483647).