Basic Hardware and Function 245
7. Instructions
FUN 236 XFER Expanded data transfer (Inverter connection mode)
Expression
Input [ A XFER B C ] Output
Function
This function is provided to control Toshiba Inverters VF-A7/G7/S9 connected on the RS-485 line.
When the RS-485 port operation mode is set to the Inverter mode (SW56 = 3), the T1-16S can
perform the following functions for up to 63 Inverters.
(1) Cyclically scans the Inverters and sends/receives the following data to/from each Inverter.
Send to Inverter: Frequency reference write and Operation command write (Run, Stop, etc.)
Receive from Inverter: Operating frequency monitor and Output terminal status monitor
(2) Cyclically scans the Inverters and receives the following data from each Inverter.
Receive from Inverter: Operating frequency monitor and Output terminal status monitor
(3) Sends a specified Read command to a specified Inverter and stores the response data.
(4) Sends a specified Write command with the command data to a specified Inverter.
(5) Sends a specified Write command with the command data to all the connected inverters as
broadcast.
Execution condition
Input Operation Output ERF
OFF No execution OFF
ON Normal execution ON
When error is occurred (see Note) ON Set
Operand
Name Device Register Constant Index
X Y R S T. C. XWYWRWSW T C D I J K
A Data table
√√√√√√√
B Inverter No.
√√√√√√√
C RS-485 port
√√√√√√
Parameters
Data table designation Parameter and status RS-485 port designation
A Register type code B Inverter number C Fixed to H0030
A+1 Leading address B+1 Operation mode C+1 Fixed to 0
B+2 Execution status
B+3 Communication error code
B+4 Inverter communication
B+5 status map
B+6 (each bit shows each
B+7 Inverter status)
Data table designation (A, A+1):
Register Type code (A) Leading address (A+1)
RW register H0003 0 to 255
D register H0004 0 to 4095