6.7.2.10. Disabling/Enabling Data Channels
Data channels can be temporarily disabled, which can reduce the read/write wear on the disk-on-chip. The
ALL_01 channel of the M360E, for example, is disabled by default.
To disable a data channel, follow the instruction shown in Section 6.7.2.2 then press:
Edit Data Channel Menu
SETUP X.X 0) CONC: ATIMER, 1, 900
PREV NEXT INS DEL EDIT PRNT EXIT
Exits to the main
Data Acquisition
menu
SETUP X.X NAME:CONC
<SET SET> EDIT PRINT EXIT
SETUP X.X CHANNEL ENABLE:ON
<SET SET> EDIT PRINT EXIT
ENTR accepts the new
setting and returns to the
previous menu.
EXIT ignores the new setting
and returns to the previous
menu.
SETUP X.X CHANNEL ENABLE:ON
OFF ENTR EXIT
Toggle key to turn
channel ON or OFF
Press SET> key until…
From the DATA ACQUISITION menu
(see Section 6.7.2.2)
6.7.2.11. HOLDOFF Feature
The iDAS HOLDOFF feature allows to prevent data collection during calibrations and during the
DAS_HOLDOFF period enabled and specified in the VARS (Section 6.12). To enable or disable the HOLDOFF,
follow the instruction shown in Section 6.7.2.2 then press:
Edit Data Channel Menu
SETUP X.X 0) CONC: ATIMER, 1, 900
PREV NEXT INS DEL EDIT PRNT EXIT
Exits to the main
Data Acquisition
menu
SETUP X.X NAME:CONC
<SET SET> EDIT PRINT EXIT
SETUP X.X CAL HOLD OFF:ON
SET> EDIT PRINT EXIT
ENTR accepts the new
setting and returns to the
previous menu.
EXIT ignores the new setting
and returns to the previous
menu.
SETUP X.X CAL HOLD OFF:ON
ON ENTR EXIT
Toggle key to turn
HOLDOFF ON or OFF
Press SET> key until…
From the DATA ACQUISITION menu
(see Section 6.7.2.2)
74 05232 Rev B3