8 Chime
Circuits with this attribute will cause the internal
sounders and remote keypad sounders to
generate a two tone “chime” sound if the
circuit is activated. The users may enable or
disable the chime feature, or select it to
operate when the system is unset or part-set.
The “Chime” attribute may only be assigned to
Night, 24hr, Auxiliary, Final Exit and Exit
Terminator circuit types.
System Timers [1.5]
The system timers are as follows:
00 2nd Alarm Time
This timer controls the duration of the “Second
Alarm” output. This timer has a working range of
000-199 seconds.
01 No of Re-Arms
At the end of the bell duration time the system
re-arms all circuits that are healthy. Circuits that
are still in an alarm are isolated until they
change to a healthy condition. This counter
controls the number of times that a "circuit" will
re-arm before it is locked out of the system. This
counter has a working range of 000-199.
02 Settle Time
When setting the system by “Final Exit” or “Exit
Terminator”, detectors that are on the exit route
sometimes take 3-4 seconds to settle after
activation. The delay programmed in this timer
is used to allow these detectors to settle before
the system or area is set. This timer has a
working range of 000-199 seconds.
03 Part Set Comms Delay
Wh en th e sy stem is pa rt-s et th e
communication of an alarm signal to the
central station can be delayed by the value
set in this timer. If the timer is set to 199 the
part-set communications are disabled. This
timer has a working range of 000-199 seconds.
04 Exit Time
This timer sets the delay between the user
initiating the exit procedure and the system (or
area) actually setting. If during the exit time an
“Exit Terminator” circuit is activated the exit
time is cancelled and the system sets
immediately. This timer has a working range of
000-199 seconds.
05 Entry Time
When the system is set or part-set, and the entry
procedure is initiated, the entry timer starts to
count down. If a valid user passcode has not
been entered when the timer reaches zero,
the internal sounders are activated and the
“2nd Entry” timer is started. This timer has a
working range of 000-199 seconds.
28
Engineer’s Menu 1 TS690R Installation Manual
Enter circuit type:
= Not Used
= Night
= 24hr
= PA Silent
Circuit Type
4
0
1
2
3
Enter circuit No.
e.g. 04
= Fire
= Auxiliary
= Final Exit
5
6
7
e.g. 7 for Final Exit
Select attributes:
= ccessA
= KnockD
= estT
1
2
3
= esetR
= onitoredM
= ntryE
5
6
7
e.g. 8 for chime
= PA Audible
4
= mitO4 = himeC8
= Exit Terminator
= Key Point
8
9
E / MENU 1
CCT NO.--
NIGHT
F.EXIT
C
Program Circuits Flowchart