![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/5/b7/5b76f384-e349-4aae-a348-19debcadbefa/5b76f384-e349-4aae-a348-19debcadbefa-bg8.png)
PowerLogic
TM
EM4800 Series 930-110-01-B.00
Introduction 04/2011
© 201 Schneider Electric All Rights Reserved2
Table 1: PowerLogic EM4800 series meter specifications
Specification PowerLogic EM4833 meter PowerLogic EM4880 meter PowerLogic EM4805 meter
Dimensions Height: 13.125 in. (33.5 cm)
Width: 12 in. (30.5 cm)
Depth: 2.125 in. (5.5 cm)
Height: 13.125 in. (33.5 cm)
Width: 12 in. (30.5 cm)
Depth: 2.125 in. (5.5 cm)
Height: 13.125 in. (33.5 cm)
Width: 17 in. (44 cm)
Depth: 2.125 in. (5.5 cm)
Weight 8.77 lb (3.98 kg) 8.77 lb (3.98 kg) 11.9 lb (5.4 kg)
Sense voltage 100V to 300V 50/60Hz
2W+N+Protective Earth Wye
3W+N+Protective Earth Wye
3W+Protective Earth Delta
100V to 300V 50/60Hz
2W+N+Protective Earth Wye
3W+N+Protective Earth Wye
3W+Protective Earth Delta
100V to 300V 50/60Hz
2W+N+Protective Earth Wye
3W+N+Protective Earth Wye
3W+Protective Earth Delta
Control voltage and current North America: 120V 125 mA 60 Hz
International: 230-240V 63 mA
50/60 Hz
North America: 120V 125 mA 60 Hz
International: 230-240V 63 mA
50/60 Hz
North America: 120V 125 mA 60 Hz
International: 230-240V 63 mA
50/60 Hz
Current transformers
Measurement Category III
0.333 V secondary CT
Note: All CTs used with the product
must be UL recognized/listed.
80 mA secondary CT
200 A primary CT
Meter burden: 4.04 ohms
CT burden: 20 ohms
Part number: METSECT80200
Note: All CTs used with the product
must be UL recognized/listed.
5 A secondary CT
Note: All CTs used with the product
must be UL recognized/listed.
Measurement accuracy
(Accuracy compliant when
used with 0.3% CTs)
ANSI C12.20 Class 0.5
IEC 62053-22 Class 0.5S
ANSI C12.20 Class 0.5
IEC 62053-22 Class 0.5S
Measurement Canada Approved
EG07 compliant
ANSI C12.20 Class 0.5
IEC 62053-22 Class 0.5S
Measurement Canada Approved
EG07 compliant
Pulse inputs 1 and 2 Dry form A and solid-state form A
compatible
Maximum frequency 10 Hz
Minimum pulse width 20 ms
Dry form A and solid-state form A
compatible
Maximum frequency 10 Hz
Minimum pulse width 20 ms
Dry form A and solid-state form A
compatible
Maximum frequency 10 Hz
Minimum pulse width 20 ms
Non-volatile memory storage 120 days in 15-minute intervals 120 days in 15-minute intervals 120 days in 15-minute intervals
Onboard modem V.90 V.90 V.90
Onboard Ethernet port 10/100 Mb/s 10/100 Mb/s 10/100 Mb/s
Serial port 115 kb/s 115 kb/s 115 kb/s
Fuse rating (F1) North America:120V: T125 mA, 250V
International 230V: T63 mA, 250V
North America:120V: T125 mA, 250V
International 230V: T63 mA, 250V
North America:120V: T125 mA, 250V
International 230V: T63 mA, 250V
Environmental
Operating temperature -40 to 70
o
C -40 to 70
o
C -40 to 70
o
C
Operating humidity 5% to 90% non-condensing 5% to 90% non-condensing 5% to 90% non-condensing
Usage environment Indoor or enclosed outdoor
environment
Indoor or enclosed outdoor
environment
Indoor or enclosed outdoor
environment
Maximum altitude 9843 ft (3000 m) 9843 ft (3000 m) 9843 ft (3000 m)
Pollution degree 2 2 2