For a 480Y/277V three-phase wye panel with the 120V variant of the
meter:
Connect meter terminal A to the voltage disconnect phase A (red wire)
Connect meter terminal B to the voltage disconnect phase B (black
wire)
Connect meter terminal C to the voltage disconnect phase C (blue wire)
Connect meter neutral terminal to neutral bar in the voltage disconnect
panel (white wire)
Connect earth wire to earth post using lug provided
From the auxiliary power transformer, connect 120V auxiliary power to
AUXA and AUXN on the meter (see Figure 9)
Figure 9: PowerLogic EM4800 meter 480Y/277V three-phase wye
service connection
8
5
7
6
10
2
1
4
3
9
Legend:
1 BX cable
2 Earth
3 AuxA (red)
4 AuxN (white)
5 Phase C (blue)
6 Sense voltage terminal block (J3)
7 Neutral (white)
8 Phase A (red)
9 Phase B (black)
10 0.75-inch (1.9-cm) strain relief