For a 208Y/120V three-phase wye panel with the 120V variant of the
meter:
Connect meter terminal A to the voltage disconnect phase A (red wire)
Connect meter terminal B to the voltage disconnect phase B (black
wire)
Connect meter terminal C to the voltage disconnect phase C (blue wire)
Connect meter neutral terminal to neutral bar in the voltage disconnect
panel (white wire)
Connect earth wire to earth post using lug provided
Install power supply shorting jumpers (see Figure 7)
Figure 7: PowerLogic EM4800 meter 208Y/120V three-phase wye
service connection
Legend:
1 BX cable
2 Earth
3 Phase C (blue)
4 Phase B (black)
5 Shorting jumper
6 Sense voltage terminal block (J3)
7 Neutral (white)
8 Phase A (red)
9 0.75-inch (1.9-cm) strain relief