In the ADVANCED MENU screen, press the <NEXT> soft
key until the Mpp Range Limit % VOC screen appears.
Press the <1/2> soft key until FULL appears. When
nished, press the <NEXT> soft key to go to the Sweep
Interval screen.
In the Sweep Interval screen, press the <-MIN> soft key to
adjust the Sweep Interval from 03 minutes (default) to 00
minutes. Press the <NEXT> soft key until the MPPT Mode
screen appears.
To pick between Auto Sweep or U-Pick % MPPT Mode and
determine the MX60’s operating Voc percentage, press
the <NEXT> soft key until the MPPT Mode menu appears.
Press the <MODE> soft key to interchange between Auto
Sweep and U-Pick%Voc modes. Re-entering the password
might be required. Press the <NEXT> soft key in the
ADVANCED MENU until the Park Mpp screen appears.
ADVANCED MENU
Mpp Range Limit %Voc
min max
EXIT NEXT 1/2 90%
ADVANCED MENU
Sweep Interval
03 Minutes
EXIT NEXT -MIN MAX+
ADVANCED MENU
MPPT Mode
Auto Sweep
EXIT NEXT nonGT MODE