Data Channel Properties
Property Description Initial
Setting
Setting
Range
NAME The data channel’s
name (primarily used
for RS-232 access and
reports)
“NONE” Up to 6
letters or
numbers
EVENT The event which
triggers this data
channel to record a
sample or issue a
report
ATIMER Any of the
events listed
in the table
of triggering
events shown
above
PARAMETER
S
The number of
parameters sampled
1 1 to 10
REPORT
PERIOD
The amount of time
between each report
000:01:00 000:00:01 to
366:23:59
(Days:Hours:
Minutes)
NUMBER OF
RECORDS
How many reports
will be stored in the
data file
100 1 to 1000
RS-232
REPORT
Indicates whether or
not a report will be
printed on the RS-232
channel
OFF OFF or ON
CHANNEL
ENABLED
ON ON or OFF
CAL. HOLD
OFF
ON ON or OFF
NAME
This property is primarily for the user’s convenience, and the user should select
meaningful names (you can give a data channel any name you want, up to six characters
long). When you edit this property you should see a display like the following:
Blank names (all dashes) or duplicate names should be avoided because they won’t be
accessible from the RS-232 interface.
EVENT
This property designates the event that will trigger data collection. Since this could be a
diagnostic tool, it might be useful to read the parameter that is associated with the events
such as the calibration. A data channel can be triggered by only one event. If you must
trigger collection of the same data by multiple events, then you can create multiple data
channels and trigger each one with a different event. The list of available triggering
events is shown in following table.
P/N 02163G1 Teledyne API Model 300 CO Analyzer Instruction Manual - Page 45