Wiring up the analogue
module
13
Wiring up the analogue module
X Short-circuit any unused channels on the analogue input
module.
X Short-circuit any unused current outputs on the analogue
output module (2 to 3 channels).
X Only use shielded cables for connection to external equipment.
X Route the cables separately from power leads or signal cables
that carry differential voltages.
X Depending on the prevailing electromagnetic environment, one
or both ends of the shielding should be grounded.
X Lay the AC supply power cables in separate ducts to those used
for signal or data cables.
X Lay signal and data cables as close as possible to the grounded
surfaces of the switchgear cabinet.