Toshiba LF414 Automobile Parts User Manual


 
- 28 -
6F8A0870
4.4 Grounding
CAUTION
Do not wire cables and replace parts
when power is supplied.
Do not work on piping and wiring with wet hands.
DON’T
Wiring work and replacing
parts in the power-on state
may cause electric shock.
DON’T
Wet hands may result in electric shock.
(1) Grounding of the LF414/LF600F, LF414/LF610F type
Ground as shown in Figure 4.10. Make the grounding wire as short as possible. Use grounding
wire material of IV wire 5.5mm
2
or more. Do not share a grounding wire with other
instruments where grounding current may flow. (An independent grounding is preferable.)
Figure 4.10 Grounding the LF414/LF600F, LF414/LF610F Type
Grounding terminal
If the piping material is conductive, connect
the grounding wires to the both ends of the
piping flange.
If the piping material is non-conductive, perform
grounding (grounding resistance 100Ω or less).
Conductive material pipe
Example: Metal, etc.
Piping of non-conductive material
Example: Resin or metal piping whose
inside is resin-lined, etc.
Integral
Grounding wire
grounding resistance
100Ω or less