18 © Copyright 2010 Schneider Electric All Rights Reserved. F-26642-8
Wiring Requirements Control and Power Leads
See Table-3 for power wiring data. Refer to Figure-1 through Figure-3 for typical wiring
applications.
Note: Class 2 control and power lead wiring must be routed separately from line voltage
wiring and any other non-class 2 circuits. Line voltage, auxiliary switch, and auxiliary switch
leads must be connected to a class 1 circuit.
Table-3 Power Wiring Data.
SIEBE
MA-7501-502
AM-673
Figure-4 Mounting Multiple Actuators.
Actuator Voltage Part Number
Maximum Wire Run in ft. (m) (5% Voltage Drop)
14 AWG 16 AWG 18 AWG
24 Vac
22-30 Vdc
MA4X-7153
330 (101) 200 (61) 130 (40)
MA4X-7153-502
24 Vac
22-30 Vdc
MA40-7043
1100 (335) 700 (213) 440 (134)
MA40-7043-501
24 Vac
22-30 Vdc
MA4X-7073
600 (183) 500 (152) 254 (77)
MA4X-7073-502