Multiquip DCA25SSIU3 Automobile Parts User Manual


 
PAGE 16 — DCA25SSIU3 60 HZ GENERATOR • OPERATION AND PARTS MANUAL — REV. #0 (12/20/10)
GENERATOR
This MQ Power generator (Figure 3) is a high quality
portable (requires a trailer for transport) power source for
telecom sites, lighting facilities, power tools, submersible
pumps and other industrial and construction machinery.
ENGINE OPERATING PANEL
The “Engine Operating Panel” is provided with the following:
Tachometer
Oil Pressure Gauge
Water Temperature Alarm Lamp
Oil Pressure Alarm Lamp
Charging Ammeter Gauge
Pre-Heat Lamp
Panel Light
Panel Light Switch
Starter Switch
Water Temperature Gauge
Fuel Gauge
Fuel Filter Water Level Alarm Lamp
GENERATOR CONTROL PANEL
The “Generator Control Panel” is provided with the following:
Frequency Meter (Hz)
AC Ammeter (Amps)
AC Voltmeter (Volts)
Ammeter Change-Over Switch
Voltmeter Change-Over Switch
Voltage Regulator
3-Pole, 60 amp Main Circuit Breaker
“Control Box” (located behind the Gen. Control Panel)
• Automatic Voltage Regulator
• Current Transformer
• Over-Current Relay
• Starter Relay
• Voltage Selector Switch
OUTPUT TERMINAL PANEL
The “Output Terminal Panel” is provided with the following:
Two 250 VAC output receptacles (CS-6369), 50 amps
Two auxilliary circuit breakers, 250V @50 amps
Two 125 VAC output receptacles, (GFCI), 20 amps
Two GFCI circuit breakers, 125V@ 20amps
Five output terminal lugs (3Ø power)
OPEN DELTA EXCITATION SYSTEM
This generator is equipped with the state of the art “Open-
Delta” excitation system. The open delta system consist
of an electrically independent winding wound among
stationary windings of the AC output section.
There are four connections of the open delta A, B, C and
D. During steady state loads, the power from the voltage
regulator is supplied from the parallel connections of A to
B, A to D, and C to D. These three phases of the voltage
input to the voltage regulator are then rectifi ed and are the
excitation current for the exciter section.
When a heavy load, such as a motor starting or a short
circuit occurs, the automatic voltage regulator (AVR)
switches the confi guration of the open delta to the series
connection of B to C. This has the effect of adding the
voltages of each phase to provide higher excitation to the
exciter section and thus better voltage response during the
application of heavy loads.
The connections of the AVR to the AC output windings are
for sensing only. No power is required from these windings.
The open-delta design provides virtually unlimited excitation
current, offering maximum motor starting capabilities. The
excitation does not have a “fi xed ceiling” and responds
according the demands of the required load.
ENGINE
This generator unit incorporates an ISUZU BV-4LE2 diesel
engine. This engine is designed to meet every performance
requirement for the generator. Reference Table 2 for engine
specifi cations.
In keeping with MQ Power’s policy of constantly improving
its products, the specifi cations quoted herein are subject
to change without prior notice.
ELECTRIC GOVERNOR SYSTEM (OPTION)
The electric governor system controls the RPMs of the engine.
When the engine demand increases or decreases, the
governor system regulates the frequency variation to ±.25%.
EXTENSION CABLES
When electric power is to be provided to various tools or
loads at some distance from the generator, extension cords
are normally used. Cables should be sized to allow for
distance in length and amperage so that the voltage drop
between the generator and point of use (load) is held to
a minimum. Use the cable selection chart (Table 6) as a
guide for selecting proper extension cable size.
GENERAL INFORMATION