7.5L DIESEL SERVICE RECOMMENDATIONS
GENERAC POWER SYSTEMS, INC.
RECOMMENDED SCHEDULED MAINTENANCE PROGRAM
SERVICE WORK TO BE PERFORMED BY FACTORY-TRAINED PERSONNEL ONLY.
DEALER INFORMATION
NAME:
ACCOUNT #:
ADDRESS:
PHONE:
TECHNICIAN:
SIGNATURE:
OWNER INFORMA
TION
NAME:
ADDRESS:
SITE:
PHONE:
SIGNATURE:
PURCHASE DATE: START-UP DATE:
APPLICATION: Standby Power Prime Power Rental/Trailerized
GENERATOR & TRANSFER SWITCH INFORMATION
GENERA
TOR
MODEL NUMBER:
SERIAL NUMBER:
TRANSFER SWITCH
MODEL NUMBER:
SERIAL NUMBER:
HOUR METER READING
at Completion of the Inspection
:
WARNING!
To prevent injury, perform the following steps in the order indicated before starting any maintenance:
Disable the generator set from starting and/or connecting to the load by setting the control panel
Auto-Off-Manual switch to the “OFF” position.
Remove the control panel fuse.
Turn off the battery charger.
Remove the negative battery cable.
NOTE:
The battery charger must be turned off BEFORE removing the battery cable to prevent an over current con-
dition from burning out sensitive control panel components and circuits.
Following all maintenance, reverse these steps to insure the unit is returned to standby setup for normal
operation when required.
!
!