Campbell Manufacturing 10164-L Remote Starter User Manual


 
CSI MODEL 10164-L SAMPLER CONTROL CABLE
FOR USE WITH ISCO AND SIGMA AUTOSAMPLERS
2
CR10 Program (Subroutine 98 in Program Table 3)
* 3 Table 3 Subroutines
1: Beginning of Subroutine (P85)
1: 98 Subroutine Number
2: Z=Z+1 (P32)
1: 10 Z Loc [ Sample_No ]
3: Do (P86)
1: 10 Set high Flag 0 (output
flag)
4: Set Active Storage Area (P80)
1: 1 Final Storage Area 1
2: 400 Array ID or location
5: Real Time (P77)
1: 1110 Year,Day,Hour-Minute
6: Sample (P70)
1: 1 Reps
2: 10 Loc [ Sample_No ]
7: End (P95) ;of Subroutine Number 98
End Table 3
Inhibit Sampler’s Program
Wire color CR10 21X BDR320
purple G Ground GND
(Isco) green C1 Control 1 C1
(Sigma) brown C1 Control 1 C1
clear G Ground GND
To inhibit an Isco sampler from running its own
program, set control port 1 low using a program
control instruction such as Instruction 86. To
allow the sampler to run its program, set it high.
NOTE: The logic for Sigma samplers is just
the opposite. A high signal inhibits the
sampler.
Example for inhibiting an Isco sampler's
program:
Do (P86)
1: 51 Set Port 1 low ;(41 would
set it high)
Technical details of cable design:
Wire color Via
Connector pin
brown direct D
green direct F
purple direct B
yellow solid state none (controls C)
relay circuit
red solid state C
relay circuit
orange 20Kohm E
resistor
clear cable shield no connection