Electrical
Data
Table E-1: Electrical Data
Model: WPWD
024 036 042 048 060 072
Voltage 208-230/60hz/1phase
Compressor RLA 11.4 15 18.4 20.4 28 32.1
Compressor LRA 56 73 95 109 169 169
Minimum Circuit Ampacity 16 21 25.8 28.6 39 45
Max Fuse Size 25 30 40 45 60 70
Aux Pump Amps 2.5 2.5 2.5 2.5 2.5 2.5
Desuperheater Min Cir Ampacity 14.3 18.8 23 25.5 35 40.1
Desuperheater Pump RLA 0.4 0.4 0.4 0.4 0.4 0.4
Voltage 208-230/60hz/3phase
Compressor RLA - 10.7 11.4 13.9 20 19.3
Compressor LRA - 63 77 88 123 137
Minimum Circuit Ampacity - 15 16 19.4 28 27
Max Fuse Size - 20 25 30 45 40
Aux Pump Amps - 2.5 2.5 2.5 2.5 2.5
Desuperheater Min Cir Ampacity - 13.4 14.3 17.4 25 24.1
Desuperheater Pump RLA - 0.4 0.4 0.4 0.4 0.4
Voltage 460/60hz/3phase
Compressor RLA - 5 5.7 7.1 7.5 10
Compressor LRA - 31 39 44 49.5 62
Minimum Circuit Ampacity - 7 8 10 10.5 14
Max Fuse Size - 15 15 15 15 20
Aux Pump Amps - 2.5 2.5 2.5 2.5 2.5
Desuperheater Min Cir Ampacity - 6.3 7.1 8.9 9.4 12.5
Desuperheater Pump RLA - 0.4 0.4 0.4 0.4 0.4
Voltage 575/60hz/3phase
Compressor RLA - - - - 6.4 7.8
Compressor LRA - - - - 40 50
Minimum Circuit Ampacity - - - - 9 11
Max Fuse Size - - - - 15 15
Aux Pump Amps - - - - 2.5 2.5
Desuperheater Min Cir Ampacity - - - - 8 9.8
Desuperheater Pump RLA - - - - 0.4 0.4
Voltage 265/60hz/1phase
Compressor RLA 9.6 14.3 16.4 17.1 - -
Compressor LRA 47 71 83 98 - -
Minimum Circuit Ampacity 13.5 20 23 24 - -
Max Fuse Size 20 30 35 35 - -
Aux Pump Amps 2.5 2.5 2.5 2.5 - -
Desuperheater Min Cir Ampacity 12 17.9 20.5 21.4 - -
Desuperheater Pump RLA 0.4 0.4 0.4 0.4 - -