RT-PRC002-EN
Electrical
Data
(High Efficiency)
Table ED-10— Unit Wiring With Electric Heat (Single Point Connection) — High Efficiency, TXV/Face-Split Evaporator Coil and
151/181/ 241 Reheat Option(Downflow Only), continued
Standard Indoor Motor Oversize Indoor Motor
To Use Heater Heater Control Max Fuse Size or Max Fuse Size or
Tons With Model No. KW Rating Stages MCA Max Circuit MCA Max Circuit
Breaker
2
Breaker
1,2
575 Volts Three Phase
AYDHTRKW18A 18.0 1 27 30 30 30
12½ TCD151CW AYDHTRMW36A 36.0 2 49 50 51 60
AYDHTRKW54A 54.0 2 70 70 73 80
AYDHTRKW18A 18.0 1 30 40 32 40
TCD181CW AYDHTRMW36A 36.0 2 49 50 51 60
15
AYDHTRKW54A 54.0 2 70 70 73 80
TCD181CW *AYDHTRKW18A 18.0 1 28 35 30 40
AYDHTRMW36A 36.0 2 51 60 55 60
17½ TCD211CW AYDHTRLW54A 54.0 2 73 80 77 80
AYDHTRKW72A 72.0 2 95 100 98 100
AYDHTRMW36A 36.0 2 51 60 55 60
20 TCD241CW AYDHTRLW54A 54.0 2 73 80 77 80
AYDHTRKW72A 72.0 2 95 100 98 100
AYDHTRMW36A 36.0 2 55 60 — —
25 TCD301CW AYDHTRLW54A 54.0 2 77 80 — —
AYDHTRKW72A 72.0 2 98 100 — —
Notes:
1. HACR type circuit breaker per NEC.
2. Values do not include power exhaust accessory.
3. Do not use with oversized motor.
* Applies only to Dehumidification (Hot Gas Reheat) Models