44 BCXC-SVX01B-EN
Controls Interface
• Zone setpoint
• Current zone temperature
• Fan mode selection (off-auto-high-low)
For optimal system performance, blower coil units can operate as part of an Integrated Comfort™
System (ICS) building automation system controlled by Tracer Summit®. The controller is linked
directly to the Summit control panel via a twisted pair communication wire, requiring no additional
interface device (i.e., a command unit). The Trane ICS system can monitor or override ZN520
control points. This includes such points as temperature and output positions.
Rover Service Software
This windows-based software package option allows field service personnel to easily monitor,
save, download, and configure Tracer™ controllers through a communication link from a portable
computer. When connected to the communication link, Rover™ can view any Tracer controller that
is on the same communication link.
Table 15. Tracer controller input/output summary
Tracer™ controller
ZN010 ZN510 ZN520
Binary outputs
2-speed fan •••
2-position hydronic valve • • •
2-position mixing box damper • •
1-stage electric heat • • •
Modulating mixed air damper •
Modulating hydronic valve •
2-stage electric heat •
Reheat (hydronic) •
Generic •••
Binary inputs
Condensate overflow detection • • •
Low temperature detection • • •
Occupancy •••
Generic input •••
Analog inputs
Zone temperature • • •
Setpoint • • •
Fan mode: auto, high, low •••
Entering water •••
Discharge air •••
Outside air •
Generic
Notes:
1. The generic input and output are for use with a Tracer Summit® systems only.
2. Contact the factory for recommendations regarding steam coil valve selections compatible with Tracer™ ZN controllers.