12-6-7. Combustion Blower Motor Abnormal Revolution
Failure Display on Outdoor Unit PCB: ● ●● ●● ●
Check combustion blower motor.
➀ Measure AC voltage at blower motor connector (CN05) (under heating operation, during combustion).
In case of abnormality ➞ Replace outdoor unit PCB.
In case of abnormality ➞ Replace combustion blower motor.
➁ Disconnect combustion blower motor connector, and measure resistance at connector.
*Use a circuit tester (set to AC range).
*Use a circuit tester (set to Ω range).
Normal PUR – PUR AC 30 – 115 V
*Use a circuit tester (set to AC range).
Normal BLK – BLK AC 104 – 126 V
*Use a circuit tester (set to AC range).
Normal BLK – BLK AC 104 – 125 V
Normal BLK – BLK 300 – 500 Ω
Normal BLK – BLK 300 – 500 Ω
Normal PUR – PUR 10 – 30 Ω
12-6-8. ON/OFF Valve Failure
Failure Display on Outdoor Unit PCB: ● ● ●● ●●
Check ON/OFF valve coil (CN06).
➀ Measure AC voltage at the ON/OFF valve coil connector (under heating operation, during combustion).
In case of abnormality ➞ Replace outdoor unit PCB.
In case of abnormality ➞ Replace ON/OFF valve coil.
➁ Disconnect ON/OFF valve connector and measure resistance at connector.
*Use a circuit tester (set to Ω range).
12-6-9. Reversing Valve Failure
Failure Display on Outdoor Unit PCB: ● ● ●● ●
Check reversing valve coil.
➀ Measure AC voltage at reversing valve coil connector (CN03) (under heating operation, during combustion).
In case of abnormality ➞ Replace outdoor unit PCB.
In case of abnormality ➞ Replace reversing valve coil.
➁ Disconnect reversing valve coil connector and measure resistance at connector.
Caution: Reversing valve failure can be displayed when there is a shortage of refrigerant. Therefore if the
above check shows normal, check the amount of refrigerant.
*Use a circuit tester (set to Ω range).