A SERVICE OF

logo

Publication 1783-UM002C-EN-P - April 2009 15
Chapter 1
Status Indicators
The switches and expansion modules have these status indicators.
Switch and Port Status Indicators
VRTAA
31793-M
EIP Mod Status Indicator
EIP Net Status Indicator
Setup Status Indicator
PWR A Status
Indicator
PWR B Status Indicator
Dual-purpose Port
Status Indicator
Port Status Indicator
Indicator State Description
EIP Mod
(EtherNet/IP module status)
Off No power. Check the power supply and cabling.
Solid green The switch is operating properly.
Flashing
green The switch has not been configured as a managed switch (for example,
Express Setup was not performed, no IP address, no password). The
switch is operating as an unmanaged switch.
Flashing red A recoverable minor fault, such as an incorrect configuration, has
occurred.
Solid red A non-recoverable major fault has occurred. Cycle power. If the
problem persists, contact Rockwell Automation Technical Support.
Flashing green/red The switch is performing a power-on self-test (POST).
EIP Net
(EtherNet/IP network
status)
Off No power or no IP address.
Check the power supply and cabling.
Make sure switch is properly configured.
Solid green The device has at least one established EtherNet/IP connection.
Flashing
green No EtherNet/IP connection yet, but the switch has obtained an IP
address.
Flashing red EtherNet/IP connection has timed out.
Solid red Duplicate IP address. The switch has detected that its IP address is
already in use.
Flashing green/red The switch is performing a power-on self-test (POST).