12. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN
12 - 15
MELSEC
GOT
12.6 A1S62DA module monitor
12.6.1 Operation monitor
1)
4)
5)
6)
7)
13
12
11
5)
6)
7)
8)
9)
10)
8)
10)
9)
2) 3)
No. Contents of display
Buffer memory address
to reference (decimal)
1)
The specified enable/disable status for the analog output of each channel is
displayed.
0: Enable 1: Disable
0
2)
The channel 1 digital input value is displayed.
1
3)
The channel 2 digital input value is displayed.
2
4)
The ON/OFF status of the I/O signal corresponding to the PLC CPU is displayed. The
I/O signal is ON when displayed in a reverse display.
5)
The current input value, a value between -4000 to 4000 for the digital input value of
channels 1 and 2, is displayed in a graph as a percentage ranging from 0 to 100%.
6)
The current input value, a value between -8000 to 8000 for the digital input value of
channels 1 and 2, is displayed in a graph as a percentage ranging from 0 to 100%.
7)
The current input value, a value between -12000 to 12000 for the digital input value of
channels 1 and 2, is displayed in a graph as a percentage ranging from 0 to 100%.
8)
The current input value, a value between 0 to 4000 for the digital input value of
channels 1 and 2, is displayed in a graph as a percentage ranging from 0 to 100%.
9)
The current input value, a value between 0 to 8000 for the digital input value of
channels 1 and 2, is displayed in a graph as a percentage ranging from 0 to 100%.
10)
The current input value, a value between 0 to 12000 for the digital input value of
channels 1 and 2, is displayed in a graph as a percentage ranging from 0 to 100%.
1, 2
11)
When the channel 1 digital input value was set outside the allowable setting range, a
check code is displayed.
10
12)
When the channel 2 digital input value was set outside the allowable setting range, a
check code is displayed.
11
13)
The set resolution selection is displayed.
1: 1/4000 2: 1/8000 3: 1/12000
9