SPECIFICATIONS - continued
GEH-7252 10 May 2003
g
GE Capacitor & Power Quality Product
s
Figure 5
5% and 8% Filter Power Factor vs Load
Leading PF For All Load
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
1.10
0 20406080100120
Percent Filter Load
Power Factor
Typical Worst Case
Performance With Unbalanced Line Voltage (Typical)
Table 4
All Components at Nominal Values
and Worse Case Service Conditions
8% Filter 100% Load 5% Filter 100% Load
Nominal THID 5.12% 3.93%
1% Unbalance 5.28% 4.06%
2% Unbalance 5.82% 4.47%
3% Unbalance 6.62% 5.10%
8% Filter 30% Load 5% Filter 30% Load
Nominal THID 10.13% 7.06%
1% Unbalance 10.61% 7.45%
2% Unbalance 12.11% 8.21%
3% Unbalance 14.30% 10.46%