Mounting instructions and important information for operation and installation
D.EM-03.08-S-en-BF
2006-06-14
Schischek GmbH Germany D-90579 Langenzenn, Mühlsteig 45, Gewerbegebiet V, Tel. ++49 (0)9101-90810, Fax ++49 (0)9101-908177, Email ExMax@schischek.de
RedMax-5.10-BF RedMax-15-BF
Special makes RedMax-..-VA/-CT
EXPLOSIONPROOF
Important information for installation and operation
Mounting of quarter turn valves
Mounting on air dampers with double squared shaft connection
RedSwitch - adaptable external EEx-d aux. switches
RedBox - adaptable terminal box
EEx-i safety temperature sensor - FireSafe
Extra information "EL" (see additional data sheet)
extra technical information, versions of circuit diagrams and failure indication
Extra information "ME" (see additional data sheet)
extra technical information, dimensions, installation instruction and illustration
Important information for routine test
A. Installation, commissioning, maintenance
The cable of the actuator must be installed in a fixed position and protected against
mechanical and thermical damage. In acc. with operation RedMax actuators are
maintenance free. Nevertheless maintenace must comply with regional standards,
rules and regulations. The actuators must not be opened by the customer. For outdoor
installation a protective housing against rain, snow and sun should be applied to the
actuator, as well as a constant supply at terminal 1 and 2 for the integral heater. For
electrical connection inside hazardous areas an terminal box is requested (e.g. type
RedBox).
Example: you have to cut the supply voltage before opening an EEx-e terminal box
B. Shaft connection, selection of running time, heater
RedMax actuators are equipped with a direct coupling double squared shaft connection
of 12 x 12 mm. For round shafts an adaptor is available (Accessory type KB-S).
The housing of the actuator is axially symmetrically built to select open/close direction
of the spring return function by left/right mounting.
In acc. to the actuator type 5 different motor running times and 2 different spring return
running times can be selscted on site. The integral heater is for ambient temperatures
down to -40°C.
C. Working with 3 sec. motor running time
See extra information EL.
D. 3-pos control mode
See extra information EL.
E. Spring return
Spring return function works if the supply voltage (terminal 1 or 2) is cut. In the event
of an electrical interruption, the spring returns to its end position.
F. Operation at an ambient temperature below - 20°C
See extra information EL.
G. Excess temperature
In acc. to the ATEX rules and regulations EEx actuators must be protected against
excess temperature. An internal thermostat guarantees the temperature class in the
event of failure. If this thermostat is working the actuator must be sent to the factory.
RedMax actuators are equipped with an additional temperature sensor to stop the
actuator before reaching this max. temperature. In this case the failure must be
eliminated immediately on site.
Details see extra information ME.
Details see extra information ME.
RedSwitch is an accessory to RedMax actuators size
S, fixing directly onto the actuator. RedSwitch are aux.
switches with with 2 potential free contacts, adustable
on site. The electrical wiring needs an terminal box.
For electrical connection of an RedMax inside the hazar
dous area an terminal box is required.
RedBox-BF for RedMax-5.10-BF and RedMax-15-BF.
To adapt the RedBox direct to the actuator housing an
additional accessory type MKK-S is required.
The safety thermostat type FireSafe is passive and
potential free for use in intrinsic safe circuits, directly
connectable to the EEx-i circuit of the RedMax-...-BF
actuators. The sensor switches at an ambient temperature
of 72°C and starts the fail safe spring return function of
the actuator. Sensor with manufacturer certificate in acc.
with ATEX.
For periodic inspection of fire dampers cut of the the supply line (cut off the current
of the actuator)
The switch contact on FireSafe is only for test aims of actuators function.