V4055F,G FLUID POWER ACTUATOR WITH MANUAL CONTROL
65-0029-02 2
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information,
or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech
Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.
SPECIFICATIONS
Models:
V4055G Fluid Power Actuator with Manual Control-for use
with the V5055 valve. Provides ON-OFF control. Rated for 5
PSI.
V4055F-Same as V4055G except: for use with V5055C only.
Meets UL and FM proof of closure requirements.
a
Maximum total connected power to both switches (if used) is
1800 VA.
Nominal Opening Time: 13 seconds:
Closing Time: 1 sec maximum when de-energized.
Ambient Operating Temperature Rating:
-40°F to +150°F (-40°C to +66°C) for 60 Hz models; -10°F to
+158°F (-23°C to +70°C) for 50 Hz and 50/60 Hz models.
Mounting Means:
Actuator mounts directly to valve bonnet with 2 setscrews,
positioned 90 angular degrees apart. Valve and actuator
can be mounted in any position.
Mounting Dimensions: See Fig. 1.
Accessories:
133568 Auxiliary Switch Bag Assembly.
133569 Valve-Closed Indication Switch Bag Assembly.
Approvals: UL and FM. IRI Approvable.
Electrical Ratings: See Table 2.
OPERATION
1. The red READY TO OPEN light will be on if there is
power to the actuator and the rocker switch is in the cen-
ter position.
2. To open the valve depress the rocker switch to the
VALVE OPEN position and hold until the valve is open
(Red READY TO OPEN light turns off). The valve will
close if the rocker switch is released from the VALVE
OPEN position with the red READY TO OPEN light on.
3. To close the valve depress rocker switch to VALVE
CLOSED position. The rocker switch stays in the valve
closed position when released.
4. The valve automatically closes on power loss. It must be
manually reopened using the rocker switch.
Table 1. Auxiliary Switch And Valve-closed Indication Switch
Ratings: 112 hp (0.37 kW)
a
LOAD 120 V 240 V
Full Load 9.8 A 4.9A
Locked Rotor 58.5 A 29.4 A
Table 2. Electrical Ratings.
Voltage and
Frequency
Opening (Fast) Holding
InrushWAVAWAVA
120/60 5.4 71.0 1.33 160 9.5 0.12 14