CyberPower RMCARD303 Remote Starter User Manual


 
Method 2: Using a command prompt
1. Obtain the MAC address from the label on the Remote Management
Card. Each Management Card has a unique MAC address.
2. Use the ARP command to set the IP address.
Example:
To assign the IP Address 192.168.10.134 for the Remote Management
Card, which has a MAC address of 00-0C-15-0A-0A-0A you will type in
the following command prompt from a PC connected to the same
network as the Remote Management Card.
(1) Type in “arp-s 192.168.10.134 00-0C-15-0A-0A-0A” then press
Enter.
3. Use the Ping command to assign a size of 123 bytes to the IP.
(1) Type in “ping 192.168.10.134 -l 123” then press Enter.
(2) If the replies are received, your computer can communicate with the
IP address.
7. You will need to enter a User
Name and Password for the
Remote Management Card
in the authentication window,
as shown in figure 3.
*Default user name: cyber;
Default password: cyber.
8. If IP address is successful,
you will see a message that
the IP set up is OK, as
shown in figure 4.
WEB INTERFACE Login Account
There are two user account types.
- Administrator (default username : cyber ; default password : cyber)
- Viewer (default username : device ; default password : cyber)
The administrator can access full functions, including enable/disable the
Viewer account, and the viewer can access the read function but can not
control or change any setting.
Conformance Approvals
FCC Warning
This equipment has been tested and found to comply with the limits for a
Class A Digital Device, pursuant to Part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference in residential installation. This equipment generates, uses
and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely
to cause harmful interference in which case the user will be required to
correct the interference at his own expense.
Any special accessories needed for compliance must be specified in the
instruction.
This device complies with part 15 of the FCC Rules. Operation is subject
to the following two conditions: (1) This device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
Te Class A digital apparatus meets all requirements of the Canadian
Interference-Causing Equipment Regulation.
Cet appareil numerique de la class A respecte toutes les exigencies
du Reglement sur le materiel brouilleur du Canada.
Figure 3. Authentication window.
Figure 4. Setup IP Address successfully message.
Trouble Shooting
Problem
Unable to configure
the Remote
Management Card
by method 1 or
method 2
Unable to ping the
Management Card
Lost the user name
and password
Solution
1. Check the LED status , the normal condition
is when yellow and green led are both on.
If green led is off :
►Check if the Remote Management Card is
properly seated in the UPS and the UPS
power is on.
If yellow led is off :
►Check if the network connection is valid.
2. Check if the operated PC is on the same
physical network as Management Card is .
1. Use method 1 and method 2 to get correct IP
address of the Management Card.
2. If the operated PC is on the different physical
network from the Management Card, verify
the setting of subnet mask and the IP
address of gateway.
Please refer to the “Reset to Default Setting /
Recover from a Lost Password” part in the
user’s manual.