Table 16 Fan Performance, 48TF012 Horizontal Discharge Units (SI)
LEGEND
NOTES:
1.
Boldface
indicates field-supplied drive required. (See Note 5.)
2. indicates field-supplied motor and drive are required.
3. Values include losses for filters, unit casing, and wet coils.
4. Use of a field-supplied motor may affect wire sizing. Contact
your Carrier representative to verify.
5. Standard drive range is 9.5 to 13.0 r/s. All other speeds require
a field-supplied drive.
6. Maximum continuous BkW is 1.79. Extensive motor and electri-
cal testing on these units ensures that the full range of the
motor can be utilized with confidence. Using the fan motors up
to the ratings shown will not result in nuisance tripping or pre-
mature motor failure. Unit warranty will not be affected.
7. Interpolation is permissible. Do not extrapolate.
AIRFLOW
(L/s)
EXTERNAL STATIC PRESSURE (Pa)
50
100 150
200
250
R/s BkW R/s BkW R/s BkW R/s BkW R/s BkW
1500 9.1 0.49
10.5 0.63 11.6 0.77 12.6 0.89
13.5 0.99
1550 9.4 0.54
10.7 0.68 11.8 0.82 12.8 0.96
13.7 1.06
1600
9.6 0.59 10.9 0.73 12.0 0.88 13.0 1.02
13.9 1.14
1650
9.8 0.65 11.1 0.80 12.2 0.95
13.2 1.09 14.1 1.22
1700
10.1 0.71 11.3 0.86 12.4 1.01
13.4 1.16 14.2 3.10
1750
10.3 0.77 11.5 0.92 12.6 1.07
13.5 1.23 14.4 1.38
1800
10.6 0.84 11.7 0.98 12.8 1.14
13.7 1.30 14.6 1.47
1850
10.8 0.92 11.9 1.04 13.0 1.21
13.9 1.39 14.8 1.55
1900
11.1 1.00 12.1 1.14
13.2 1.29 14.1 1.47 15.0 1.64
1950
11.3 1.09 12.3 1.22
13.4 1.38 14.3 1.55 15.2 1.72
2000
11.6 1.18 12.6 1.31
13.6 1.47 14.5 1.65
15.3 1.82
2050
11.9 1.28 12.8 1.40
13.8 1.56 14.7 1.73
15.5 1.92
2100
12.1 1.38 13.0 1.50
14.0 1.64
14.9 1.82 15.8 2.02
2150
12.4 1.49
13.2 1.60 14.2 1.73
15.1 1.93 15.9 2.13
2200
12.7 1.61
13.4 1.70
14.4 1.83 15.3 2.04 16.1 2.24
2300
12.9 1.74
13.7 1.81 14.6 1.93 15.5 2.15 ——
2350
13.2 1.86 13.9 1.93 14.8 2.03 15.7 2.27 ——
2400
13.5 2.00 14.2 2.05 15.0 2.14 ————
2500
——
14.4 2.14 15.2 2.25 ————
AIRFLOW
(L/s)
EXTERNAL STATIC PRESSURE (Pa)
300
350 400
450
500
R/s BkW R/s BkW R/s BkW R/s BkW R/s BkW
1500 14.5 1.13 15.2 1.22 16.1 1.40 16.8 1.54
17.7 1.82
1550 14.6 1.20 15.4 1.30 16.2 1.43 16.9 1.60
17.8 1.86
1600 14.8 1.26 15.6 1.40 16.3 1.50 17.1 1.68
17.9 1.91
1650 14.9 1.33 15.7 1.48 16.5 1.60 17.2 1.72
18.0 1.97
1700 15.0 1.42 15.9 1.56 16.7 1.70
17.3 1.81 18.0 1.97
1750 15.2 1.51 16.0 1.64 16.8 1.79
17.5 1.91 18.2 2.04
1800 15.4 1.61 16.2 1.73
17.0 1.89 17.7 2.03 18.3 2.15
1850 15.6 1.71
16.3 1.84 17.1 1.98 17.8 2.15 18.5 2.27
1900
15.8 1.80 16.5 1.94 17.2 2.07 18.0 2.24 18.7 2.40
1950
16.0 1.91 16.7 2.06 17.4 2.19 ————
2000
16.2 2.01 16.9 2.17 17.6 2.31 ————
2050
16.3 2.10 17.1 2.29 ——————
2100
16.5 2.21 ————————
2150
16.7 2.32 ————————
2200
16.9 2.43 ————————
2300
——————————
2350
——————————
2400
——————————
2500
——————————
BkW
Fan Input kW x Motor Efficiency
R/s
Revolutions Per Second of Blower Wheel