TOSHIBA G8000 Series UPS
Installation Planning Guide for 100kVA UPS
Standard System: 480V Input, 480Y/277V Output
Rev. 1.03 Page 1 of 1 G8000-IPG-100kVA
General Mechanical Information
Dimensions
(W x D x H)
Weight
Approximate Full-Load
Heat Loss
Inches Lbs. Btu/Hr
55.1 x 31.5 x 78.75 2,756 30,840
Primary AC Input (480V 3-Phase / 3-Wire)
Maximum Input Power
Demand
Suggested External
Overcurrent Protection
Suggested Minimum Feeder
Wire Size Per Phase
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA PF Amps Amps AWG or kcmil at 75º C Temp. Rating Feet
100 >0.98 120 150 AT (1) x 1/0 480
Alternate (Bypass) AC Input (480V 3-Phase / 4-Wire)
Maximum Input Power
Demand
Suggested External
Overcurrent Protection
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA PF Amps Amps AWG or kcmil at 75º C Temp. Rating Feet
100 0.8 120 150 AT (1) x 1/0 / (1) x 4/0 380
Battery Input (360VDC Nominal)
Battery Capacity Required
for Full Load Output
Maximum Discharge
at Full Load Output
Suggested External
Overcurrent Protection
Suggested Minimum Feeder
Wire Size Per Phase
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kWB Amps DC Amps AWG or kcmil at 75º C Temp. Rating Feet
86.9 301 400 AT (2) x 3/0 70
AC Output (480/277V 3-Phase / 4-Wire)
Rated Output Power
Suggested External
Overcurrent Protection
Suggested Minimum Feeder
Wire Size Per Phase / Neutral
Suggested Maximum Feeder Length
For Min. Wire Size in Steel Conduit
kVA PF Amps Amps AWG or kcmil at 75º C Temp. Rating Feet
100 0.8 120 150 AT (1) x 1/0 / (1) x 4/0 380
11. Sizing calculations based on the following assumptions:
- Not more than 3 current-carrying conductors installed in
steel conduit in ambient temperature of 30 degrees C.
- Temperature rating of conductors and terminals: 90 deg. C.
- Feeder distance calculations based on NEC Tables 8 and 9
data, allowing for 2% AC voltage drop.
- Reference: 2002 NEC Handbook. Consult latest edition of
applicable national and local codes for possible variations.
12. Ratings of wires and overcurrent devices are suggested
minimums. Consult with a registered Professional Engineer
within your local area for proper size selections.
Important Notes:
1. Maximum Current required at Primary AC Input based on full
load output and maximum battery charging current.
2. Output load conductors are to be installed in separate
conduit from input conductors.
3. Control wires and power wires are to be installed in separate
conduits.
4. Recommended AC input and output overcurrent protection
based on continuous full load current per NEC.
5. Wiring shall comply with all applicable national and local
electrical codes.
6. Grounding conductors to be sized per NEC Article 250-122.
Neutral conductors to be sized per NEC Article 310.15.
- Primary AC Input: 3φ, 4-wire + ground.
- Alternate AC Input: 3φ, 4-wire + ground.
- AC Output: 3φ, 4-wire + ground.
- DC Input: 2-wire (Positive/Negative) + ground.
7. Nominal battery voltage based on the use of VRLA type
batteries (2.0 volts/cell nominal).
8. Maximum battery discharge current based on lowest
permissible discharge voltage of 1.6 VPC.
9. DC wires should be sized to allow not more than a 2-volt
drop at maximum discharge current.
10. Weights do not include batteries or other auxiliary equipment
external to the UPS.