Murphy SV-Series Automobile Parts User Manual


 
SV-99026B page 1 of 2
SV-Series
Solenoid Operated Fuel Shutoff Valve
Diesel Engines
Diesel Driven Pumps and
Compressors
High Pressure Models
Select from 12 or 24 VDC Models
Description
The SV-series valve is a normally closed valve that
opens when current is supplied from the battery
through a magnetic switch. Temperature, level, or
pressure SWICHGAGE
®
instruments installed on
the engine and pump or compressor, trip the mag-
netic switch, breaking the circuit from the battery
which closes the valve and stops the engine.
The SV-12 valve operates on 12VDC, has a 1/4 NPT
inlet and outlet, and a full 3/16 in. (5 mm) orifice.
24 VDC (SV-24) is optional The SV valves open
against 30 psi. (207 kPa) [2.07 bar] inlet pressure.
Greater Flow Rate Valve
Special series SV valve is available with a 1/4 in.
(6 mm) orifice which opens against maximum
pressure of 15 psi (103 kPa) [1.03 bar]. This
valve is recommended where greater flow is
required, and only static head or low transfer
pump pressures are encountered.
High Pressure Valves
SV-HP series valves open against diesel fuel
transfer pump pressure up to 60 psi (414 kPa)
[4.14 bar]. Models are available for 12 or 24 volt
DC systems. The orifice is 1/4 in. (6 mm), using
the same inlet/outlet and options as standard SV.
Specifications
Electrical Rating: 12 VDC, 10 watts
Orifice: 3/16 in. (5 mm) diameter (optional 1/4 in.
[6 mm] diameter). See chart above, right.
Body Connections: 1/4 NPT inlet/outlet
Maximum Opening Pressure:
3/16 in. (5 mm) orifice: 30 psi (207 kPa) [2.07 bar]
1/4 in. (6 mm) orifice: 15 psi (103 kPa) [1.03 bar]
SV-HP (High Pressure model)
Orifice: 1/4 in. (6 mm) diameter. See chart below.
Maximum Opening Pressure:
60 psi (414 kPa) [4.14 bar].
Dimensions
Shipping Weight: 1 lb. 6 oz. (0.68 kg)
Shipping Dimension: 3 x 2-3/4 Sx 2-3/4 in.
(76 x 70 x 70 mm)
Warranty
A limited warranty on materials and workmanship
is given with this FW Murphy product. A copy of
the warranty may be viewed or printed by going to
www.fwmurphy.com/support/warranty.htm
BATTERY GROUND
FLOW
3/4 in.
(19 mm)
3/8 in.
(9 mm)
11/16 in.
(17 mm)
2-1/8 in.
(54 mm)
3/8 in.
(9 mm)
2-3/16 in.
(56 mm)
2-11/16 in.
(68 mm)
2-5/32 in.
(55 mm)
Brass Body
10-24 NC-2B
2 Mounting Holes
Differential
Pressure
3/16 Orifice 1/4 Orifice
Gallons per
Minute
Liters per
Minute
1 2 5 10 20 30 1 2 5 10 15
.48 .68 1.1 1.5 2.2 2.6 .72 1.05 1.65 2.35 2.70
2.012.85 4.62 6.3 9.2410.92 3.02 4.416.93 9.87 11.34
How to Order
See the diagram below, example: SV–12–HP
CAUTION: Do NOT use the SV valves with distribu-
tor type injection pumps. For use with DIESEL ONLY.
Coil Voltage
12 =
12 VDC
24 =
24 VDC
HP =
High Pressure
Orifice
Blank (non-“HP” models) =
3/16 in. (5mm) dia.
Blank (“HP” models) =
1/4 in. (6 mm) dia.
4 =
1/4 in. (6 mm) dia. (non-“HP” models only)
SV– __ – __ – __
A Screw 80-04-1412
B Coil Replacement Kit
12 volt kit 55-01-0141
24 volt kit 55-01-0145
C Core Repair Kit (Std mdls)55-01-0155
C Core Repair Kit (HP mdls) 55-01-0156
D Valve Body: 3/16 Orifice
1/4 NPT x 1/4 NPT(std.) 55-05-0194
D Valve Body: 1/4 Orifice
1/4 NPT x 1/4 NPT 55-05-0193
PPaarrtt DDeessccrriippttiioonn
PPaarrtt NNuummbbeerr
SV Repair Parts
Callouts diagram shown on page 2
CCaalllloouutt
SV-99026B
Revised 6-05
Catalog Section 55
(00-02-0375)
Diesel-Fuel Shutoff Valves