![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/5/b8/5b84690c-355d-461c-b422-01db054a3bcc/5b84690c-355d-461c-b422-01db054a3bcc-bg1.png)
k
VA 5.0 7.5-10
W
idth (A) 36” 36”
D
epth (B) 24” 24”
H
eight (C) 80” 80”
W
idth (D) N/A 29”
Operates incandescent, magnetic and electronic ballast fluorescent, high power factor compact fluorescent, and high intensity discharge (HID) lamp types.
How to Specify:
LOT Series Uninterruptible Power Supplies LOT
Page 1 of 2 5 kVA - 10 kVA Single Phase UPS System
J
ob Inf
ormation Type:
J
ob Name:
Cat. No.:
Lamp(s):
Notes:
Lightolier a Genlyte Company
www
.lightolier
.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
W
e r
eser
ve the right to change details of design, materials and finish.
© 2006 Genlyte Gr
oup LLC (Lightolier Division) • A0406
Overall Characteristics
• 87% throughput efficiency, 85% emergency efficiency
• Operating temperature range 32°F (0°C) to 104°F (40°C)
• Fault current rating 42kAIC
• Audible noise less than 50dB at 3 ft on “A” weighted scale
• Automatic low battery voltage disconnect
Electrical
• Sine Wave Output
•
Double conversion, no inter
r
uption
• Voltage regulation ±2%
•
Fr
equency r
egulation - synchr
onized to utility
, fr
ee r
unning 60 Hz,
±
0.5%
• Output voltage distortion maximum 3% THD with linear load
• Load power factor capability 0.7 lead to 0.7 lag
•
Overload capacity 125% for 10 seconds
• Input power factor correcting to 0.99
• Frequency range 60Hz, ±2.5%
•
Input har
monic cur
r
ent distortion <5% THD
•
UL 1449, ANSI,IEEE C62, 41 sur
ge suppression
• Completely solid-state Pulse Width Modulation (PWM) inverter
•
Inter
nal, make befor
e br
eak maintenance by-pass
•
Standar
d, UL 924 compliant, 90 minute batter
y backup
• UL 924 auxiliary equipment 10 and 20 minute backup available
• Microprocessor control and diagnostic system
• LCD readout system status panel
• Local 25 even logging/display
•
User pr
ogrammable automatic testing
•
Load integrity testing
• Fault annunciating audible alarm
•
Cur
r
ent limiting star
t sequence
•
Optional output cir
cuit br
eakers (OCB) and cir
cuit breakers with trip alarm (OCBA)
• Optional normally off load (NOL) energizes only during power outage, normally off
load with time delay (TDT) also available
Housing
•
Free standing, NEMA 1 enclosure
• Seismic anchoring compatible
• Lockable control access panel
Applications
• The solid-state Pulse Width Modulated (PWM) inverter offers enhanced load
compatibility
• Provides conditioned, uninterruptible power for other types of critical loads.
Consult factory for non-lighting load applications.
LOT
SERIES
I
NPUT OUTPUT UNIT BACK-UP NOL OUTPUT # ON 2ND # OF NOL NOL # OF NOL
VOLTAGE VOLTAGE SIZE DURATION CKT BRKRS VOLTAGE CKT BRKRS VOLTAGE 2nd VOLTAGE
L
OT = Single
P
hase
Uninterruptible
P
ower
Supplies
5
.0 = 5.0 kVA
7.5 = 7.5 kVA
10.0 = 10.0 kVA
A
= 120 V*
G
= 120/240V
J = 277 V
L = 120/208V
0
= None
1 = Yes
T = NOL w/ TDT
0
0X = Hardwire
01X = 1 OCB
02X = 2 OCB
03X = 3 OCB
04X = 4 OCB
:
:
20X = 20 OCB
------------------
01A = 1 OCBA
02A = 2 OCBA
03A = 3 OCBA
:
:
10A = 10 OCBA
Max. Pole
Spaces 20
0
0 = 2nd
Voltage
Hardwire or no
2nd Vo
ltage
01
02
03
:
:
19
A = 1
B = 2
C
= 3
D
= 4
E = 5
F
= 6
G = 7
H = 8
I = 9
J = 10
K = 11
L = 12
M = 13
N = 14
O = 15
P = 16
Q = 17
R = 18
S = 19
T = 20
Z = No NOL
1
= First
2 = Second
3 = Both
0 = No NOL
A = 1
B = 2
C
= 3
D
= 4
E = 5
F
= 6
G = 7
H = 8
I = 9
J = 10
K = 11
L = 12
M = 13
N = 14
O = 15
P = 16
Q = 17
R = 18
S = 19
Z = No NOL
A = 120 V*
G = 120/240V
J
= 277 V
L = 120/208V
Y
= 120/277V
S = 90 min
X = 10 min
Y = 20 min
(A)
(
B)
(
C)
Electronics
Cabinet
(D)
Battery
Cabinet
* Not available on 7.5 and 10.0 kVA