Emerson LT410 Radar Detector User Manual


 
Product Specification Sheet page 1 11/02 (Rev. 0)
LIQUI-TECT
®
410
Point Leak Detection Sensor
Description
The Liqui-tect 410
(LT410) provides a
single-point detection
of leaks. The point
detection sensor has
two gold-plated
sensing probes to
prevent corrosion
resistance and to
provide accurate
readings. The LT410
constantly monitors
points for leaks,
internal faults and power failures and warns of any
abnormal conditions. Mounting brackets allow for
sensor height adjustment and leveling.
The LT410 is the ideal solution for sensing leaks under
a raised computer floor or air conditioning drip pans.
Two independent outputs provide added flexibility
with the capacity to signal both a local alarm panel
and a remote building management system or external
equipment, such as motorized water shut-off valves.
The LT410 is also ideally suited for the following:
Placement on Subfloor
Under Cooling Support Equipment
Specifications
Dimensions-Top, Front & Side Views
Wiring Interconnections
Ordering Information
Applications Locations
• Glycol, Chilled
Water Cooling
• Humidification
Feed Water Piping
• Condensate Pumps
and Drains
• Unit and Ceiling
Auxiliary Drip Pans
• Overhead Piping
Troughs
• Large-Scale Network Control
Centers
• Data Centers
• Server Rooms - Closets
• Unattended Remote Shelters
• Mechanical Equipment Rooms
• Sensitive Areas With
Overhead Piping
• Industrial Process Control
Rooms
* Output connections to external alarm monitoring panels
such as the Liebert contact closure alarm panels
Leak detection
zone (directly
beneath unit)
To a Liebert
environmental
unit and
an optional*
monitoring
panel
To external
power
supply or
directly
from
unit
LT410
Liqui-tect 410 Sensor
Power requirements 24 VAC 100 mA, 50/60 Hz, 3 VA (max.)
Dimensions
W x D x H
6.35" x 2.25" x 4.46"
(161.2 mm x 57.2 mm x 113.2 mm)
Weight (assembled) 2.0 lbs (0.9 kg)
Metal enclosure NEMA 1, IP 30
Environmental Conditions
Operating temperature 50°F to 104°F (10°C to 40°C)
Operating humidity
10% to 95% relative humidity
(non-condensing)
Operating altitude 0 to 10,000 ft (0 to 3,048 m)
Output Relays
Contact rating 2 Form-C; 3 A rating at 24 VAC
Agency Listings
UL UL916
C-UL C22.2, No. 205-M1983
CE Yes
FCC Compliance 47 CFR, Part 15
Red Wires Orange Wires Yellow Wires
24 V, AC/DC
@0.10A, 50-60Hz, DC
Class 2 Circuit Only
Alarm Contact Rating
24 VAC @ 3A
Class 2 Circuit Only
Alarm Contact Rating
24 VAC @ 3A
Class 2 Circuit Only
Product
Number
Quantity Description
LT410 Point Leak Detection Sensor
5.85"
(148.5mm)
TOP VIEW
Form-C relay
outputs &
power wiring
connection
4.46"
(113.2mm)
FRONT VIEW
Adjustable
probe height
0.0–0.5"
(0.0–12.7mm)
2.25"
(57.2mm)
SIDE VIEW
6.35"
(161.2mm)
Shipping weight: 2 Ibs (0.9 kg)
Mounting holes: #8 screws
Power
Power
1-NO
1-NC
1-COM
2-NO
2-NC
2-COM
Gold-plated
probes
Height adjustable